Page view 2
Rated input current (at
maximum load)
3.4A
Nominal Input
Voltage(s) Supported
230V AC
UPS input connection
type
C14 inlet
UPS input connection
description
C14 inlet accepts user-supplied AC power cord with country specific plug.
Input circuit breaker 10A
BATTERY
Full load runtime
(minutes)
9 min. (700w)
Half load runtime
(minutes)
21 min. (350w)
DC system voltage (VDC) 24
Battery recharge rate
(included batteries)
4.5 hours from 10% to 90%
Replacement battery
cartridge (internal UPS
battery replacement)
RBC92-2U
Battery Access Front panel battery access door
Battery replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 159 to 282
Overvoltage correction Input voltages between 245 and 282 are reduced by 12%
Undervoltage correction Input voltages between 159 and 199 are boosted by 14%
LEDS ALARMS & SWITCHES
LED Indicators 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Alarms Audible alarm indicates power-failure, overload and low-battery conditions
Alarm cancel operation Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
Switches 2 Switches control off/on power status and alarm-cancel/self-test operation
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
480
UPS AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Installation form factors
supported with included
accessories
4 post 19 inch rackmount (mounting rail kit included)