Output Voltage Regulation (Line
Mode)
230V (-15%, +6% )
Output Voltage Regulation (Battery
Mode)
+/- 5%
Output Receptacles (8) C13; (1) C19
Included Output Power Cables Includes 3 C13 to C14 output power cables
Load Management Receptacles Three switchable two-outlet C13 load banks
Output Circuit Breakers 10A (x2) - each breaker protects 4 C13 outlets, C19 outlet does not include a breaker
Output AC Waveform (AC Mode) Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 15A
Nominal Input Voltage(s) Supported 230V AC
UPS Input Connection Type C20 inlet
UPS Input Connection Description User supplies input cabling with C19 output connection
Input Circuit Breakers 20A
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 4 min. (2250w)
Half Load Runtime (min.) 11 min. (1125w)
Expandable Battery Runtime Extended runtime supported via optional external battery packs
External Battery Pack Compatibility
BP48V24-2U
(limit 1);
BP48V60RT-3U
(multi-pack compatible);
BP48V27-2US
(multi-pack compatible)
DC System Voltage (VDC) 48
Battery Recharge Rate (Included
Batteries)
Less than 4.5 hours from 10% to 90% (typical, full load discharge)
Internal UPS Replacement Battery
Cartridge
RBC94-2U
Battery Access Front panel battery access door
Battery Replacement Description Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 158 to 278
Overvoltage Correction Input voltages between 244 and 278 are reduced by 12%
Undervoltage Correction Input voltages between 182 and 206 are boosted by 12%
Severe Undervoltage Correction Input voltages between 158 and 182 are boosted by 24%