Tripp Lite SMX3000XLRT2UA Datasheet Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 5
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
UPS Input Connection Description
IEC320-C20 input connection accepts a variety of user supplied detachable C19 output cordsets to match country or
site specific power sources
Input Circuit Breakers 20A
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 3.9 min. (2700w)
Half Load Runtime (min.) 11.1 min. (1350w)
Expandable Battery Runtime Extended runtime supported via optional external battery packs
External Battery Pack Compatibility
BP48V24-2U
(limit 1);
BP48V60RT-3U
(multi-pack compatible);
BP48V27-2US
(multi-pack compatible)
DC System Voltage (VDC) 48
Battery Recharge Rate (Included
Batteries)
Less than 5 hours from 10 to 90% (typical, full load discharge)
Internal UPS Replacement Battery
Cartridge
RBC58-2U
Battery Access Front panel battery access door
Battery Replacement Description Hot-swappable, replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 158 to 278
Overvoltage Correction Input voltages between 244 and 278 are reduced by 12%
Undervoltage Correction Input voltages between 206 and 183 are boosted by 12%
Severe Undervoltage Correction Input voltages between 158 and 183 are boosted by 24%
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating
data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual
for detailed LCD configuration and monitoring options)
Switches 3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
Alarm Cancel Operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Audible Alarm Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 350
EMI / RFI AC Noise Suppression Yes
AC Suppression Response Time Instantaneous
PHYSICAL
3 / 5