NEMA 5-15P input, 6 NEMA 5-15R outlets
Two switched 3-outlet load banks support remote reboot or programmable load shedding options
Supports 2% output voltage regulation and zero transfer time in double conversion mode
Economy mode option offers enhanced efficiency, reduced power consumption and lower BTU emissions
14 minutes runtime at 50% load (675W) and 4.2 minutes at 100% load (1350W) with internal batteries
BP48V24-2U (limit 1), BP48V60RT-3U (multi-pack compatible) and BP48V27-2US (multi-pack compatible) external battery packs available (some
configurations require Tripp Lite's External Battery Configuration Software)
LCD interface reports operating mode plus 9 selectable screens of UPS data (Load % & kW, Load % & kVA, Power factor, Input volts & Hz, Output volts
& Hz, Battery volts and charge %, Minutes runtime, Capacity remaining, Kw/hr. consumption)
LCD interface also supports 16 screens of UPS configuration and setup options
4 post installation hardware included, Optional 2POSTRMKITWM enables 2 post rack / wallmount installation, Optional 2-9USTAND enables tower
placement
Single line TEL / Network surge suppression
Electronic bypass maintains utility output during a variety of UPS fault conditions
Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and
require replacement
Frequency regulation / conversion mode offers generator-compatible frequency correction or conversion of frequency from 50 to 60Hz or 60 to 50Hz
Built-in USB, RS-232, contact-closure and optional SNMPWEBCARD accessory monitoring options
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software
Specifications
OUTPUT
Output Capacity Details
ON LINE MODE: Maximum output capacity ratings is reduced to 1215 watts at 115V nominal and 1080 watts at
100V nominal; FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in
frequency regulation / conversion mode (127/120V 945 watts / 115V 850 watts / 110V 804 watts / 100V 756 watts)
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150%
load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and
frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE
bypass limits)
Output Volt Amp Capacity (VA) 1500
Output kVA Capacity (kVA) 1.5
Output Watt Capacity (Watts) 1350
Output kW Capacity (kW) 1.35
Power Factor 0.9
Crest Factor 3:1
Nominal Output Voltage(s)
Supported
100V; 110V; 115V; 120V; 127V
Nominal Voltage Details
120V factory-default nominal voltage; Less than 3% THD for linear loads and less than 5% for non-linear computer
loads
Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion