Highly efficient economy mode option
Optional SNMPWEBCARD, RELAYIOCARD and RELAYIOMINI interface modules available (RELAYIOMINI requires removal of USB interface module)
Applications utilizing the optional network communications card require two SNMPWEBCARD accessories (install one per included power module)
HID-compliant USB interface
Includes Free PowerAlert monitoring software; PowerAlert LOCAL, PowerAlert NSA and PowerAlert NMS for monitoring up to 250 SNMP-enabled UPS,
PDU and other networking devices
Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (4 required)
Optional 2-9USTAND supports upright tower placement (2 required)
Supports Emergency Power Off (EPO) via built-in interface
Front panel LEDs and LCD readout with scroll controls
LED / LCD display panel rotates for viewing in rackmount or tower configurations
External battery packs are field replaceable and hot swappable
Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)
Specifications
General Info
RoHS Y
OUTPUT
Output Capacity Details
Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30
seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power;
Double conversion mode is automatically restored as load levels are reduced to 95% or less
Output Volt Amp Capacity (VA) 20000
Output kVA Capacity (kVA) 20
Output Watt Capacity (Watts) 18000
Output kW Capacity (kW) 18
Power Factor 0.9
Crest Factor 3:1
Nominal Output Voltage(s)
Supported
200V; 208V; 220V; 230V; 240V
Nominal Voltage Details Voltage selection via front panel LCD interface
Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details
Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to
50Hz or 50Hz to 60Hz (no de-rating)
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 2%
2 / 6