Tripp Lite SU20KX Datasheet Page 2

  • Download
  • Add to my manuals
  • Print
  • Page
    / 5
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 1
Precision +/-1% output voltage regulation
Internal power and battery modules are combined in a single small-footprint tower compartment. Typical half-load/full-load runtimes are 13 min./5.5 min.
Battery runtime can be extended with optional stand-alone hardwired external battery modules (Models BP480V26B and BP480V40C, available
separately)
Front panel combination LCD/LED display includes a real-time event log screen with up to 500 events listed
Dynamic battery management screen optimizes battery function to lengthen service life and allow cold restart of the UPS
Built-in RS-232 communication port works with included PowerAlert Software to provide shutdown commands and reporting on a single server
Accessory slot accepts an optional internal SNMP card (Model SNMPWEBCARD) for remote shutdowns, reboots and more
Emergency Power Off button turns UPS output OFF and disables Bypass output
Built-in Emergency Power Off (EPO) dry-contact interface supports remote emergency shutdown in large facilities
Specifications
General Info
RoHS Y
OUTPUT
Output Volt Amp Capacity (VA) 20000
Output kVA Capacity (kVA) 20
Output Watt Capacity (Watts) 16000
Output kW Capacity (kW) 16
Power Factor 0.8
Crest Factor 3:1
Nominal Output Voltage(s)
Supported
220/380V; 230/400V; 240/415V; 3-Phase Wye
Frequency Compatibility 50 / 60 Hz
Output Voltage Regulation (Line
Mode)
+/-1%
Output Voltage Regulation (Battery
Mode)
+/-1%
Output Receptacles Hardwire
Output AC Waveform (AC Mode) Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 28A / 29A / 30A
Nominal Input Voltage(s) Supported 220/380V (3ph wye); 230/400V (3ph wye); 240/415V (3ph wye)
Nominal Input Voltage Description 3-Phase Wye, 4 wire (L1, L2, L3, N, G)
UPS Input Connection Type Hardwire
2 / 5
Page view 1
1 2 3 4 5

Comments to this Manuals

No comments