Specifications
OUTPUT
Output Capacity Details
ON LINE MODE: Maximum output capacity rating is reduced to 2430W (115V), 2295W (110V), 2160W (100V);
FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation /
conversion mode (127/120V 1890 watts, 115V 1701 watts, 110V 1607 watts, 100V 1512 watts) OVERLOAD
CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150% load for 30
seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency
are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits)
Output Volt Amp Capacity (VA) 3000
Output kVA Capacity (kVA) 3.0
Output Watt Capacity (Watts) 2700
Power Factor 0.9
Crest Factor 3:1
Nominal Output Voltage(s)
Supported
100V; 110V; 120V; 127V
Nominal Voltage Details 120V default
Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details
ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output
matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds
+/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz.
FREQUENCY REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency
when input is 40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz.
BATTERY MODE: Output is regulated to +/-0.05Hz of selected nominal.
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 3%
Output Receptacles (8) 5-15/20R; (1) L5-30R
UPS Output Receptacles (Surge
Suppression Only)
ON LINE MODE: Maximum output capacity rating is reduced to 2430W (115V), 2295W (110V), 2160W (100V);
FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation /
conversion mode (127/120V 1890 watts, 115V 1701 watts, 110V 1607 watts, 100V 1512 watts) OVERLOAD
CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150% load for 30
seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency
are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits)
Load Management Receptacles Two switchable four-outlet load banks
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 24A