Tripp Lite SU6000RT4UHV Datasheet Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and
require replacement
BP192V12-3U external battery packs are field replaceable and hot swappable
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Frequency conversion mode enables conversion of 60Hz to 50Hz or 60Hz to 50Hz (no de-rating)
Specifications
OUTPUT
Output Capacity Details
Output capacity de-rates to 4992 watts when used at 208V nominal; Supports up to 105% load continuously in
double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger
immediate bypass mode operation to support loads directly from mains power; Double conversion mode is
automatically restored as the overload is cleared
Output Volt Amp Capacity (VA) 6000
Output kVA Capacity (kVA) 6.0
Output Watt Capacity (Watts) 5400
Output kW Capacity (kW) 5.4
Power Factor 0.9
Crest Factor 3:1
Nominal Output Voltage(s)
Supported
200V; 208V; 240V
Nominal Voltage Details Voltage selection via front panel LCD interface
Frequency Compatibility 50 / 60 Hz
Frequency Compatibility Details
Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to
50Hz or 50Hz to 60Hz (no de-rating)
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 2%
Output Receptacles (2) L6-20R; (2) L6-30R
Output Receptacle Details
Output receptacles and input line cord are mounted on a detachable PDU backplate with bypass switch to enable
hot-swappable power module replacement
Output Circuit Breakers 20A breaker protects L6-20R outlets, L6-30R outlets are unbreakered
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 31.9A (200V), 30.6A (208V), 29A (220V), 27.7A (230V), 26.6A (240V)
Nominal Input Voltage(s) Supported 200V AC; 208V AC; 240V AC
3 / 6
Page view 2
1 2 3 4 5 6

Comments to this Manuals

No comments