Tripp Lite SU3000RTXLCD3U Datasheet Page 2

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 1
Economy mode option offers enhanced efficiency, reduced power consumption and lower BTU emissions
11 minutes runtime at 50% load (1350W) and 4 minutes at 100% load (2700W) with internal batteries
BP72V15-2U (limit 1), BP72V28RT-3U (multi-pack compatible) and BP72V18-2US (multi-pack compatible) external battery packs available (some
configurations require Tripp Lite's External Battery Configuration Software)
LCD interface reports operating mode plus 9 selectable screens of UPS data (Load percentage, kW & kVA, Power factor, Input voltage & frequency,
Output voltage & frequency, Battery voltage and charge percentage, Minutes runtime, Capacity remaining and Kw/hr. consumption)
LCD interface also supports 16 screens of UPS configuration and setup options
4 post installation hardware included, Optional 2POSTRMKITHD enables 2 post rack installation
Single line TEL / Network surge suppression
Electronic bypass maintains utility output during a variety of UPS fault conditions
Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and
require replacement
Frequency regulation / conversion mode offers generator-compatible frequency correction or conversion of frequency from 50 to 60Hz or 60 to 50Hz
Built-in USB, RS-232, contact-closure and optional SNMPWEBCARD accessory monitoring options
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software
Specifications
OUTPUT
Output Capacity Details
ON LINE MODE: Maximum output capacity rating is reduced to 2430W (115V), 2295W (110V) and 2160W (100V);
FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation /
conversion mode (127/120V 1890 watts / 115V 1701 watts / 110V 1606 watts / 100V 1512 watts) OVERLOAD
CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150% load for 30
seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency
are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits)
Output Volt Amp Capacity (VA) 3000
Output kVA Capacity (kVA) 3
Output Watt Capacity (Watts) 2700
Output kW Capacity (kW) 2.7
Power Factor 0.9
Crest Factor 3:1
Nominal Output Voltage(s)
Supported
100V; 110V; 115V; 120V; 127V
Nominal Voltage Details 120V factory-default nominal voltage
Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details
ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output
matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds
+/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz.
FREQUENCY REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency
input is 40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. BATTERY
MODE: Output is regulated to +/-0.05Hz.
Output Voltage Regulation (Line
Mode)
+/- 2%
2 / 6
Page view 1
1 2 3 4 5 6

Comments to this Manuals