2.4 AS400 Configuration
1. Press Enter to open the main menu of the RELAYIOCARD.
Press 1 to configure the alarm event for R1~R6.
2. Select the On Bypass, Low Battery, On Standby and Power Fail for R1~R4.
3. Press 0 to return to the main menu.
Then press 3 to configure the normally open or normally closed.
Select 3 to switch from Normal Open to Normal Closed
for Relay 3 (On Standby Event).
5. Set the dip switch SW2 to the ON position for the RELAYIOCARD to begin using the custom settings for the AS400 connection.
4. Press 0 to return to the main menu.
Press 0 to quit the configuration.
When the “Save Before Exit?” prompt appears,
select Y to save the configuration.
6. Connect the RELAYIOCARD terminals to the
AS400 DB9 connector as follows:
2. Installation and Setup (continued)
+---------------------------+
| UPS Relay Card |
+---------------------------+
Firmware Version: Relay Card V1.9
[1].Customize Output Relay
[2].Configure Input Signal
[3] Customize Normal Open or Normal Close
[0].Quit
Please Enter Your Choice =>
[4] Reset to Default
+---------------------------+
| Cus tomize O utput Rela y |
+-------- --------- ----------+
Relay S elected Event
[1].Relay1: O n Bypa ss
[2].Relay2: L ow Batt ery
[3].Relay3: O n Standby
[4].Relay4: Power Fail
[5].Relay5: O verload
[6] Relay6: UPS Disconnect
[0].Back To Previous Menu
Plea se Enter Your C hoice =>
+---------------------------+
| Customize Output Relay |
+---------------------------+
Relay Selected Event
[1].Relay1: Normal Open
[2].Relay2: Normal Open
[3].Relay3: Normal Close
[4].Relay4: Normal Open
[5].Relay5: Normal Open
[6].Relay6: Normal Open
[0].Back To Previous Menu
Please Enter Your Choice =>
+---------------------------+
| UPS Relay Card |
+---------------------------+
Firmware Version: Relay Card V1.9
[1].Customize Output Relay
[2].Configure Input Signal
[3] Customize Normal Open or Normal Close
[0].Quit
Please Enter Your Choice => 0
Save Before Exit? [Y]es. [N]o : Y
Data Saved.
[4] Reset to Default