PROGRAMMABLE RELAY I/O CARD
USER MANUAL
PRESENTATION
FEATURES
This relay I/O card is an UPS management
product with 6 relay output contacts for monitoring
the status and 1 input contact as a shutdown UPS
or a battery test command.
Features:
z Monitor UPS events.
z 6 programmable relay output contacts.
z Configurable normal open or normal close for
each relay contact.
z Configurable UPS shutdown delay time.
z Configurable input signal as shutdown UPS or
battery test.
z Has the ability to protect up to 6 computers
unattended shutdown gracefully.
TECHNICAL SPECIFICATION
TECHNICAL SPECIFICATION
Size 130 x 60 mm
Weight 200 g
Operating Temperature 0 ~ 40° C
Operating Humidity 10 ~ 80 %
Power Input 8 ~ 20V DC
Power Consumption 1.2 Watts
OUTPUT CONTACT RATING
Maximum
DC Voltage DC Current
Relay
R1~R6
24 V 1A
INPUT RATING
Maximum
DC Voltage DC Current
Input 24 V 10 mA
APPLICATION EXAMPLE
In this case we’ll use the default settings, please
set SW1 and SW2 to the OFF position. Apply
12VDC to Common contact and connect the
lamps to R1~R6 terminals. Install a push button
from the Common contact to the input terminal.
Press the button for at least 3 seconds to
shutdown the UPS remotely.
Common
G N D- R
R1
R2
R3
R4
R5
Input
+12V
Summary Alarm
Power Fail
Battery Low
On Bypass
Overload
Shutdown UPS
R6
Over Temperature
INTERNAL CIRCUIT
R1
R2
R3
R4
R5
Common
GND-R
Input
+5V
CPU Pin
R6
OUTLINE
GND-R
Common
R1
R2
R3
R4
R5
R6
Input
Tx
Rx
GND-C
SW1
SW2
I/O PINOUT
GND-R: Ground for relays
Common: 12~24VDC
Default Alarm Event
R1 Summary Alarm
R2 Power Fail
R3 Battery Low
R4 On Bypass
R5 Overload
R6 Over Temperature
Input: Remote shutdown or battery test
Tx: Transmit to PC, connect to sub9-pin2
Rx: Receive from PC, connect to sub9-pin3
GND-C: Ground for configuration Tx and Rx pins
OFF (Default) ON
SW1 Normal open
for default settings
Normal close
for default settings
SW2 Default settings Customized settings
PROGRAMMABLE CONTACTS
COMMUNICATION SETUP
1. Connect Tx to pin2, Rx to pin3 and GND-C to
pin5 of PC RS232 port.
2. In the Windows environment, launch the
Hyper- Terminal program then open the
specified COM port.
3. Set the following properties:
Baud rate: 2400, Data Bits: 8, Parity: None
Stop Bit: 1, Flow Control: None
CONFIGURATION
1. Press <Enter> to get the main menu of the
programmable relay card.
+---------------------------+
| UPS Relay Card |
+---------------------------+
Firmware Version: Relay Card V1.4
[1].Customize Output Relay
[2].Configure Input Signal
[3] Customize Normal Open or Normal Close
[0].Quit
Please Enter Your Choice =>
2. Press ‘1’ to configure the alarm event for
R1~R6.
Contacts R1~R6 can be configured for
different power events.
+---------------------------+
| Customize Output Relay |
+---------------------------+
Relay Selected Event
[1].Relay1: Summary Alarm
[2].Relay2: Power Fail
[3].Relay3: Battery Low
[4].Relay4: On Bypass
[5].Relay5: Overload
[6] Relay6: Over Temperature
[0].Back To Previous Menu
Please Enter Your Choice =>
Once the configuration is complete SW2
MUST be switched to the ON position to apply
the new settings, switch SW2 back to the OFF
position to reset to the default settings.
3. Press ‘2’ to configure the Input signal.
+---------------------------+
| Configure Input Signal |
+---------------------------+
[1].Act as Shutdown or Test: Shutdown
[2].Input Signal Confirm: 3 Seconds
[3].Delay Before Shutdown: 30 Seconds
[0].Back To Previous Menu
Please Enter Your Choice =>
In this menu, the input signal can be redefined
as shutdown UPS or battery test signal.
Meanwhile, the UPS shutdown delay time is
also adjustable to a maximum of 9999
seconds.
4. Press ‘3’ to configure the normal open or
normal close for each relay.
+---------------------------+
| Customize Output Relay |
+---------------------------+
Relay Selected Event
[1].Relay1: Normal Close
[2].Relay2: Normal Open
[3].Relay3: Normal Close
[4].Relay4: Normal Open
[5].Relay5: Normal Close
[6].Relay6: Normal Open
[0].Back To Previous Menu
Please Enter Your Choice =>
Once the configuration is complete SW2
MUST be switched to the ON position to apply
the new settings. Switch SW2 back to the
OFF position to reset to the default settings.
5. Press ‘0’ to quit this configuration session.
The system would prompt you to save or not.
Press ‘Y’ to save your settings, ‘N’ to ignore.
POWER OPTION IN WIN 2000/XP
This relay card has the ability to provide UPS
signals for Windows NT4/2000/XP/2003. First
connect the RS232 port on the PC to the relay
card as shown:
Then open the power option from control panel
and click on the UPS tab to setup the signals
polarity, select Positive for Power Fail, Low
Battery and UPS
Shutdown.
Since the R1~R6
contacts are
programmable,
the output
contacts can be
configured for 3
computers with 2
signals (power fail
and low battery) or
6 computers with
one signal (power
fail or low battery).
Note: All of the computers must have the same
earth ground potential. Connect all of the
computers input power to the same UPS.
Common
GND-R
R1
R2
R3
R4
R5
Input
Power Fail
R6
Battery Low
RTS pin7
GND pin5
CTS pin8
DCD pin1
DTR pin4
Shutdown UPS
1. Introducción
2. Instalación y Configuración
1.1 Características del Producto
RELAYIOCARD es un dispositivo de administración de UPS programable que cuenta con:
• 6 contactos de salida de relé programable
• Abertura normal o cierre normal configurables para cada cierre de relé
• Tiempo de retardo de apagado configurable del UPS
• Señal de entrada configurable para apagar el UPS o probar la batería
La RELAYIOCARD le permite:
• Monitorear el estado y los eventos del UPS
• Realizar apagados del sistema y pruebas de la batería de manera remota
1.2 Contenidos del Embalaje
Este Embalaje Contiene:
• RELAYIOCARD
• Cable de configuración
• Placas frontales
• Manual del propietario
2.1 Requisitos del Sistema
La RELAYIOCARD admite todos los sistemas UPS SmartOnline™ y sistemas UPS SmartPro™ selectos de Tripp Lite,
que incluyen SMART1050SLT, SMART1500SLT, SMART2200RMXL2U, SMX1050SLT, SMX1500SLT, SMART3000SLT,
SMART2200SLT, SM2200RMNAFTA, SMART2600RM2U, SMART3000RM2U, SMART1500CRMXL, SMART1500SLTXL,
SMART750XLa, SMX3000XLRT2U y SMX2200XLRT2U. Los sistemas admitidos ejecutarán un protocolo de UPS de
3008 o superior.
Para determinar su protocolo UPS:
1. Abra el software PowerAlert de Tripp Lite.
2. Haga clic en el botón “Misc” (Misceláneo) en la pantalla principal de la consola de PowerAlert.
3. Vea la variable del protocolo.
2.2 Configuración de Comunicaciones
1. Conecte Tx a pin 2, Rx a pin 3 y GND-C a pin 5 del puerto de RS-232 DB9.
2. En el entorno de Windows, abra el programa Hyper Terminal, luego abra el puerto COM especificado.
3. Ajuste las siguiente propiedades– velocidad en baudios: 2400, Bits de datos: 8, Paridad: Ninguna, Bit de parada: 1,
Control de flujo: Ninguno.
201011142 932815.indb 7 1/6/2011 9:15:48 AM
Page view 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 15 16

Comments to this Manuals

No comments