Important Safety Warnings
SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and
maintenance of all Tripp Lite SmartOnline Rackmount/Tower UPS Systems and their batteries. Failure to heed these warnings may affect your
warranty.
UPS Location Warnings
Install your UPS indoors, away from excess moisture or heat, direct sunlight, dust and conductive contaminants.
Install your UPS in a structurally sound area. Your UPS is extremely heavy; take care when moving and lifting the unit.
Only operate your UPS at indoor temperatures between 32° F and 104° F (between 0° C and 40° C). For best results, keep indoor
temperatures between 62° F and 84° F (between 17° C and 29° C).
Leave adequate space around all sides of the UPS for proper ventilation.
Do not install the UPS near magnetic storage media, as this may result in data corruption.
Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner will seriously inhibit the unit's
internal cooling, eventually causing product damage not covered under warranty.
UPS Connection Warnings
Isolate the UPS before working on this circuit.
Required Protective Devices and Cable Cross-Sections.
Recommended upstream protection.
UPS Power Rating Upstream Circuit Breaker
8kV
AD
curve -63A
10kVAD curve -83A
GL1
L1
2 poles circuit breaker
To UPS Normal AC source
L2(N)
L2(N)
The power supply for this unit must be single-phase rated in accordance with
the equipment nameplate. It also must be suitably grounded.
Equipment Connection Warnings
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life
support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a
flammable anesthetic mixture with air, oxygen or nitrous oxide.
Connect your UPS power modules grounding terminal to a grounding electrode conductor.
The UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS is not connected to an AC supply.
Maintenance Warnings
Your UPS power module and battery module(s) do not require routine maintenance. Do not open them for any reason. There are no user-
serviceable parts inside.
Battery Warnings
Do not operate your UPS without connecting it to an external battery module.
Connect only Tripp Lite battery modules to your UPS power modules external battery connector.
Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. Do not dispose of the
batteries in a fire. Do not open the UPS or batteries. Do not short or bridge the battery terminals with any object. Unplug and turn off the UPS
before performing battery replacement. Use tools with insulated handles. There are no user-serviceable parts inside the UPS. Battery replacement
should be performed only by authorized service personnel using the same number and type of batteries (Sealed Lead-Acid). The batteries
are recyclable. Refer to your local codes for disposal requirements or in the USA only call 1-800-SAV-LEAD or 1-800-8-BATTERY (1-800-
822-8837) or visit www.rbrc.com for recycling information. Tripp Lite offers a complete line of UPS System Replacement Battery Cartridges
(R.B.C.).Visit Tripp Lite on the Web at www.tripplite.com/support/battery/index.cfm to locate the specific replacement battery for your UPS.
Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes, and may be toxic.
Fuses should be replaced only by factory authorized personnel. Blown fuses should be replaced only with fuses of the same number and type.
Service and repair should be done only by trained personnel. During any service work to the UPS, it should be turned off or manually bypassed
via the transformer. Note that potentially lethal voltages exist within this unit as long as the battery supply
is connected.
Do not connect or disconnect battery module(s) while the UPS is operating from the battery supply or when the detachable PDU is not in bypass
mode.
During “hot-swap” battery module replacement your UPS will be unable to provide battery backup in the event of a blackout.
Only connect compatible battery module(s).
Legend.
B Contactor solenoid.
Q Mains input thermal-magnetic switch
T Tw o-pole contactor 100 A AC1; coil voltage: according to the mains input.
Remark: Q needs to use the approved component of Safety Certification.
External power
distribution unit
UPS
L
Q
B
T
N
L
N
201102160 93-2897.indb 2 3/30/2011 9:30:37 AM