Mounting (Rack)
4-Post Mounting
1
The included plastic pegs
A
will temporarily support the empty rackmount shelves
B
while
you install the permanent mounting hardware. Insert a peg near the center of the front and rear
bracket of each shelf as shown. (Each front bracket has 6 holes and each rear bracket has 3 holes.)
The pegs will snap into place.
After installing the pegs, expand each shelf to match the depth of your rack rails. The pegs will
fit through the square holes in the rack rails to support the shelves. Refer to the rack unit labels to
confirm that the shelves are level in all directions. Note: The support ledge of each shelf must
face inward.
2
Secure the shelves
B
to the mounting rails permanently using the included screws and cup
washers
C
as shown.
For 2U equipment mounting, place 4 screws total at the front and 4 screws total at the back.
For 3U equipment mounting, place 6 screws total at the front and 4 screws total at the back.
Tighten all screws before proceeding.
Warning: Do not attempt to install your equipment until you have inserted and tightened
the required screws. The plastic pegs will not support the weight of your equipment.
3
Attach mounting ears
D
to the front mounting holes of your equipment
E
using the screws
provided
F
. The ears should face forward.
4
Using an assistant, lift your equipment and slide it onto the mounting shelves. Attach your
equipment to the rack by passing the screws, nuts and washers (user-provided)
G
through its
mounting ears and into the rack rails.
5
(Optional) Attach 2 PDU hanger brackets to the right-side, rear mounting rail using included
screws and cage nuts. Important: determining where to attach your PDU hanger brackets will
depend on your rack configuration. Generally it is recommended to mount the top bracket in
the bottom two square holes of the U space that the UPS and PDU are mounted in. The second
bracket should be installed 3U measures down and placed in the top two square holes of the U.
(For example: If the PDU and UPS are mounted in 7U, the first bracket will be installed in the
bottom two square holes of 7U. The second bracket would be installed in the top two square holes
of 4U.
Mount your equipment in either a 4-post or 2-post rack or rack enclosure. The user must determine the fitness of hardware and procedures before
mounting. If hardware and procedures are not suitable for your application, contact the manufacturer of your rack or rack enclosure. The procedures
described in this manual are for common rack and rack enclosure types and may not be appropriate for all applications.
Note: The power module and battery module must be installed in separate shelves.
2-Post Mounting (Optional)
To mount your equipment in a 2-post rack, you must purchase a Tripp Lite 2-Post Rackmount Installation Kit (model: 2POSTRMKITWM, sold
separately) for each module installed. See the Installation Kit’s owner’s manual for complete mounting instructions.
3
E
D
G
F
4
1
B
B
A
A
A
2
2
B
B
B
B
C
C
C
C
7
8
6
5
4
3
Mount Here
5
201102160 93-2897.indb 3 3/30/2011 9:30:39 AM
Page view 2
1 2 3 4 5 6 7 8 ... 103 104

Comments to this Manuals

No comments