Tripp Lite SU750RTXLCD2U Owner's Manual Page 14

  • Download
  • Add to my manuals
  • Print
  • Page
    / 92
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 13
 
 
 
 
(FLASHING)
 
 
14
Operation
BYPASS MODE LEDs: INPUT, BYPASS (flashing) & OUTPUT
LEDs on.
BYPASS MODE LCD SCREEN: Operating mode and UPS load
information*
*Note: When bypass mode is set as a preference in the STANDBY MODE LCD screen, the BYPASS mode screen will alternate between BYPASS MODE with loading information
and PRESS ON KEY TO TURN UPS ON.
STANDBY MODE:
When first connected to a live power source, the UPS will automatically energize in Standby mode. The LCD panel will scroll “STANDBY
MODE / PRESS ON KEY TO START UPS” and the charger will activate as necessary, but there is no UPS output or battery backup support
availableinthismode.ToturntheUPSonfornormaloperation,pressandholdtheONbuttonuntilabeepisheard;theUPSwill
energize after a series of diagnostic tests are completed. To turn the UPS completely off from standby mode, just unplug the UPS from
itspowersource;theUPSwillreportOFFWAITINGandthefanandLCDscreenwillturnoffafterapproximately30seconds.
STANDBY MODE LEDs: INPUT LED on. STANDBY MODE LCD SCREEN (2 messages, 2 sec. each):
•STANDBYMODEandUPSloadinformation
•PRESSONKEYTOTURNONUPS(NotShown)
Note: A flashing INPUT LED indicates that input power is available, but is not stable enough to utilize. Pressing the ON button in standby mode while this LED is
blinking will “cold start” the UPS into battery mode.
STANDBY MODE LCD VIEWING OPTIONS:
When first entering STANDBY mode, the LCD screen will display load information in percentage and kilowatt units. To display additional
information screens, tap the SCROLL DOWN (“v”) button repeatedly. Additional screens include: Kilowatt hour usage, Kilowatt capacity
remaining, Runtime-remaining in minutes, Battery voltage and charge percentage, Output voltage and frequency, Input voltage and
frequency, Load Power Factor and Load percentage plus kVA capacity.
ECONOMY MODE:
Economy mode refers to an optional UPS configuration for reduced power consumption and heat output. A UPS in economy mode
reduces power consumption by suspending the double conversion [AC-to-DC / DC-to-AC] process whenever input power is already of high
enough quality to pass through to connected equipment unchanged. The UPS will automatically switch back to on-line mode if input
power quality deteriorates to ensure that connected equipment receives high quality power under all conditions. See LCD Set-Up section
under Operation for configuration info.
ECONOMY MODE LEDs: INPUT, AC/DC, ECO, OUTPUT LEDs on. ECONOMY MODE LCD SCREEN: Operating mode and UPS load
information
ECONOMY MODE LCD VIEWING OPTIONS:
When first entering ECONOMY mode, the LCD screen will display load information in percentage and kilowatt units. To display additional
information screens, tap the SCROLL DOWN (“v”) button repeatedly. Additional screens include: Kilowatt hour usage, Kilowatt capacity
remaining, Runtime-remaining in minutes, Battery voltage and charge percentage, Output voltage and frequency, Input voltage and
frequency, Load Power Factor and Load percentage plus kVA capacity.