Tripp Lite SU750RTXLCD2U Owner's Manual Page 19

  • Download
  • Add to my manuals
  • Print
  • Page
    / 92
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 18
 
 
120V*
SCROLL SELECT
 
 
60HZ*
SCROLL SELECT
 
 
WIDE*
SCROLL SELECT
Continued on page 20.
19
Operation
UPS Setup Order of Operations
To access the UPS Setup screens, press both the SCROLL (
v
) and SELECT (^) buttons simultaneously and hold for 3 seconds.
1
The OUTPUT VOLTAGE selection screen will appear.
OUTPUT VOLTAGE refers to the nominal output voltage of the UPS. This value is most
commonly set to match the prevailing country or region-specific nominal voltage. In general,
use 120V for USA and Canada, 127V for Mexico and 100V for Japan. Additional values of
110 & 115V are also available. Note: Certain voltage settings will cause automatic de-rating.
See specifications on unit label for de-rating info.
Press “SELECT” (
^
) to SET this value.
Press “SCROLL” (
v
) to advance to the next option.
Available values are: 100, 110, 115, 120 &
127V
Press SCROLL (
v
) to browse options
and press SELECT (
^
) to SET.
Factory default = 120V
2
The OUTPUT FREQUENCY selection screen will appear.
OUTPUTFREQUENCYreferstothecycles-per-second(Hz)ofUPSoutputpower.Thisvalueis
most commonly set to match the prevailing country or region-specific frequency. In general,
intheUSA,CanadaandMexicousethe60Hzfactorysetting.In100-127V50Hzlocations,
suchasJamaica,AntiguaandpartsofJapan,settheUPSto50Hz.Tosuccessfullyconfigure
yourUPStoconvertfrequencyfrom50-to-60Hzor60-to-50Hz,setBOTHtheOUTPUT
FREQUENCY to the desired setting and enable this function by setting the FREQ
CONVERSION to ENABLE.
To Change This
Setting:
Press “SELECT” (
^
)
To Advance to
the Next Screen:
Press SCROLL (
v
)
To Change This
Setting:
Press “SELECT” (
^
)
Press “SELECT” (
^
) to SET this value.
Press “SCROLL” (
v
) to advance to the next option.
Availablevaluesare:60Hz,50Hz
Scroll through available values and press
SELECT (
^
) to SET.
Factorydefault=60Hz
To Advance to
the Next Screen:
Press SCROLL (
v
)
3
The BYPASS RANGE selection screen will appear.
BYPASS RANGE: When ECONOMY MODE is enabled, this UPS will allow line voltage that’s
already of sufficient quality pass through to connected equipment unchanged. The BYPASS
RANGE control gives users the ability to control the amount of deviation from the selected
nominal voltage before automatically turning back to on-line mode. The factory setting of
WIDE is compatible with the vast majority of networking equipment. Using this control, users
of even the most sensitive equipment can utilize the UPS in economy mode by selecting
alternate preset values. Regardless of the “plus or minus” value entered, the highest bypass
voltage available is 135V. The lowest bypass voltage available is 90V (full load) and 70V
(<70% load). The “Wide” range reflects these same values (full load 90 to 135V / <70%
load 70 to 135V).
To Change This
Setting:
Press “SELECT” (
^
)
Press “SELECT” (
^
) to SET this value.
Press “SCROLL” (
v
) to advance to the next option.
Available values are: +/-5, 6, 7, 8, 9, 10, 11,
12, 13, 14, 15% & wide
Scroll through available values and press
SELECT (
^
) to SET.
Factory default = WIDE
To Advance to
the Next Screen:
Press SCROLL (
v
)
Note: The UPS must be
in Standby Mode to
change this setting.
Note: The UPS must be
in Standby Mode to
change this setting.
13-11-176-93-3156.indb 19 11/27/2013 4:24:54 PM